The AHU anomaly function detects common hard and soft faults related to a building's air handling unit(s).

Outputs

Key Performance Indicators (KPIs)

The AHU anomaly function identifies three common HARD faults and three common SOFT faults and calculates an AHU health index; this is done separately for each AHU. The AHU health index is the ratio of non-faults over the number of total faults that can be detected (six in total). If no faults were detected, the AHU health index would be 100%, and if all six faults were detected, the AHU health index would be 0%. Table 2 below is an example output of the detected faults.

AHU Health index Cooling coil Economizer Heating coil Outdoor air damper Schedule Supply air temperature
AHU 1 100% Normal Normal Normal Normal Normal Normal
AHU 2 0% Stuck Check economizer logic Stuck Stuck Check mode of operation logic Check supply air temperature reset logic
Table 1: Example output of KPIs of energy baseline function.

The three possible HARD faults are:

The three possible SOFT faults are:

Figures

The AHU anomaly function generates three sets of visuals to help put some context to the identified faults. The first generated visual plots supply air temperature as a function of outdoor air temperature; this is generated for each analyzed AHU. Figure 1 below is an example of this visual.

A generic square placeholder image with rounded corners in a figure.
Figure 1: Example plot of supply air temperature and return air temperatures as a function of outdoor air temperature, with highlighted supply air setpoint reset scheme. The return air temperatures of the coldest, warmest, and average thermal zones are also displayed.

The coolest, warmest, and average return air temperatures (zone air temperature) are also depicted. This visual is intended to inform a supply air temperature setpoint reset strategy. A setpoint reset strategy allows for higher supply air temperatures as outdoor air temperature decreases. Suboptimal supply air temperatures can result in excessive energy consumption from excessive perimeter heating use, economizing, or fan use. To guide supply air temperature setpoint adjustments, the typical 'ideal' supply air temperature range is highlighted in green. If the supply air temperature is lower than this range in the heating season, excessive use of perimeter heating and economizing may result; only a few overheating rooms may trigger this behaviour. If this is the case, consider increasing the maximum terminal airflow setpoints in these overheating rooms. If the supply air temperature is higher than this range in the cooling season, excessive fan power to deliver required necessary cooling may result; a few overcooling rooms may trigger this behaviour. If this is the case, consider decreasing the minimum terminal airflow setpoints in these overcooling rooms within reason. In either case, ensure that the airflow and temperature sensors work as intended in these rooms.

The second generated visual is a split-range controller diagram; this is generated for each analyzed AHU. This diagram depicts outdoor air damper (OA), heating coil valve (HC), and cooling coil valve (CC) position with respect to outdoor air temperature. The average fraction of active perimeter heating devices (RAD) is also shown. The four underlying color zones represent the four distinct AHU operating modes as per ASHRAE Guidelines 36: heating (red zone), economizer (yellow zone), economizer with cooling (grey zone), and cooling (blue zone). Figure 2 below is an example of the split-range controller diagram.

A generic square placeholder image with rounded corners in a figure.
Figure 2: Example of split-range controller diagram of healthy AHU operation. Note that HC represents the heating coil valve position, RAD represents the state of perimeter heaters, OA represents outdoor air damper position, and CC represents cooling coil valve position.

For healthy AHU operation, the following items should be especially considered:

The last set of generated visuals is a collection of simplified AHU diagrams. A set of four to six visuals per identified AHU are generated which depict average damper and valve positions and temperatures at characteristic operating periods. The fraction of time of operation is the percentage of the total time of the AHU's operation which exhibit the displayed damper and valve positions and temperatures. Figure 3 below is an example of the simplified AHU diagrams.

A generic square placeholder image with rounded corners in a figure.
Key Averaged measurement Units Range
A Outdoor air temperature oC -
B Return air temperature oC -
C Mixed air temperature oC -
D Supply air temperature oC -
E Outdoor air damper position % 0(closed) - 100(open)
F Heating coil valve position % 0(closed) - 100(open)
G Cooling coil valve position % 0(closed) - 100(open)
H Supply fan state % 0(inactive) - 100(fully active)
I Fraction of time of operation % 0(never occurs) - 100(always occurs)
J Fraction of active perimeter heating devices % 0(inactive) - 100(fully active)
Figure 3: Example of simplified AHU diagram.
Actively in development, an open-source project by the Data-driven Building Operation and Maintenance team within Carleton University's Building Performance Research Center.